Think about what happens when a surge hits an office building. The server room is down, the files are corrupted and the lift controller is dead in the space of a second. That's why commercial surge protection devices are so important in an office environment, in a shopping centre, in a hospital or a hotel. They're not the little strip you've got under your desk. They're fitted in the main electrical panels and protect the whole circuit.
This guide looks at how you protect a building from surges, what type of SPD goes where and how you go about selecting, installing and maintaining the right ones.
What Are Commercial Surge Protection Devices?
Commercial surge protection devices (SPDs) are devices that are fitted into the building's main panel and are designed to stop sudden voltage surges from reaching your equipment. They're connected in parallel with the supply. They're pretty much inert most of the time. When a surge does occur, they divert the extra current to earth in the order of nanoseconds, which keeps the voltage that gets to your equipment well within safe limits.
You'll hear people referring to them as commercial surge protectors; some will even go so far as to look for a commercial electric power surge protector. It's all the same thing, really. They're DIN rail devices, rated in kA and designed to take a hell of a lot more energy than your average retail power strip.
Commercial buildings need them as there's simply far more at stake (servers, HVAC drives, lifts, fire alarms, building management systems, etc). If you're just starting out, then check our Surge Protection Device technical guide will give you the basics of how an SPD works.
How to Protect a Building from Power Surges
Surge protection for buildings right across India has to contend with monsoon lightning, an unreliable power grid and heavy loads (chillers, lifts, etc.). A single SPD at the main panel is generally not sufficient, as surges are coming from three different sources: the grid, lightning and the equipment within the building itself.
The plan has a number of elements. You need a proper lightning protection system (designed to IEC 62305) to take the direct strike and a good earth so that every SPD has a safe place to discharge the surge. You then bond the metal services to the main earth bar to ensure there are no dangerous potential differences during a surge.
Then fit the SPDs at the main panel, at the sub-distribution boards and right up close to the critical equipment. Use the backup fuse or MCB as specified in the datasheet and check the SPDs regularly as each surge will take a little bit of life out of them. Each stage picks up what the one before it has missed, which is why it's better than a single large device.
Blitz makes its range of AC surge protection devices for exactly this layered approach.
Which SPD Type Is Used Where in a Commercial Building?
Under IEC 61643-11 and EN 61643-11, the SPDs are of three types (Classes I, II and III in the IEC terminology). Most of the SPDs you'll find in a building will be a mixture of these. The correct mixture will be a function of two things: how exposed the building is to lightning and how sensitive the equipment is. The type you'll see most often is Type 2.
Type 1 SPD
Type 1 strikes the incoming source in case the structure has any external lightning protection system or if the building gets its power supply through overhead lines. This is subjected to testing using a 10/350 µs lightning current wave because it can accept part of the lightning current entering through the cables. Buildings, tall structures with lightning conductors, and campuses on overhead lines constitute the usual examples. Other buildings may need only Type 2, but a lightning risk assessment is required first.
Type 2 SPD
Type 2 is the standard for main and sub-distribution boards. It is tested using an 8/20 µs waveform and protects against residual lightning surges and switching surges that are created inside the building. The AC SPDs from Blitz are classified as Type 2 (Class II). For a three-phase commercial supply, the AC SPD 3 Phase 4 Pole offers 20 kA nominal and 40 kA maximum discharge current with a voltage protection level of 1.5 kV or less.
The majority of surges in a commercial building are internal: chiller compressor turning off, lift motor turning on, transformer turning on. In a regular office block, this will be one SPD for the main board and one per floor board. That is why one SPD installed at the entrance will not be sufficient.
Type 3 SPD
Type 3 is very close to the equipment it's protecting (typically within about 10m of the load). It has a very low discharge capacity and is therefore used as the final stage of protection for things like a server rack, the reception AV or an access control panel. It does support the board-level SPD. It will never replace the SPD. A Type 3 unit on its own is not adequate for a building, as it won't be able to cope with the larger surges.
Commercial SPD Applications: Offices, Malls, Hospitals and Hotels
Every commercial building has its own mix of loads, so the risk is different in each and hence the approach to protection will be different. For a broader look at the application in other sectors, see our guide on the use of surge protection devices in homes, factories and solar plants. We're sticking with the buildings in this instance.
Offices
Offices are run off servers, network switches and workstations. They can fail quite quietly following a surge, and people can lose their work as a result. A surge protection device for use in an office building will typically be at the main panel and there will be further protection at the IT sub-board which feeds the server room.
Malls
Malls have the big chillers, big escalators, big lifts, big lighting and loads of tenant shops all switching loads throughout the day. There are SPDs at the main incomer and then SPDs on the tenant and floor boards to prevent one shop's problem affecting the next.
Hospitals
Hospitals simply can't afford a power cut. You've got imaging, you've got operating theatres, you've got ICUS, you've got emergency lighting, etc all running on a constant supply of power. The SPDs at the main panel and on the critical load boards provide an extra level of protection.
Hotels
A hotel has guest room electronics, kitchens, laundries, lifts and reservations spread across many floors. A surge on one floor board can take out the smart locks and room controls for all the guests on that floor. There are SPDs on each floor as well as on the front desk and the building management circuits.
Where to Install SPD in a Building (Layered Protection)
Envision the three areas starting from the point of entry of the electricity to the electrical system. The first area is the LV panel; here, the SPD will deal with the major incoming surges of electrical energy. The second one is the distribution board that comes from the LV main panel. The SPD will deal with whatever the previous zone has passed, as well as the surges that come from the lifts and pumps.
The third zone is the equipment itself: server rooms, building management systems, fire alarm panels, and access control. If the building has rooftop solar, there is a fourth spot, because the DC side needs its own protection. A DC surge protection device near the inverter and the panels protects them from surges on the DC cables.
Whatever commercial electric surge protector you end up going for, keep the leads between the SPD and the busbar as short as possible. Observe the manufacturer's recommendations as to cable length between stages as well, so that the SPDs work in concert. A long or looped lead will in fact add voltage that the SPD can't strip.
One simple rule of thumb: the closer the SPD is to the load the lower the voltage that will get to it, the more SPDS you end up having to buy and maintain. You'll typically have a main panel and floor boards and only add equipment-level SPDs where the load is critical.
How to Choose the Right Commercial SPD
When you're shopping for commercial surge protection devices, the datasheet is far more important than the label on the box. Get the datasheet from the supplier and read it, as that's where the real figures are. Whether you're looking at it as a commercial electric surge protector or a commercial power surge protector, those are the things to look at first.
- Supply type: Three-phase four-wire distribution needs a 4-pole unit. A single-phase panel needs a 2-pole unit such as AC SPD 1 Phase - 2 Pole.
- Voltage: Nominal voltage (Un) and maximum continuous operating voltage (Uc) should be the same as your source voltage. The Blitz AC devices have a rating of 230/415 V AC with a Uc of 320 V.
- Discharge current: In and Imax will give you the information about the amount of surge energy your device can handle. A more exposed main panel will need a higher rating.
- Protection level (up): Lower is better as this is the voltage that still gets through to your equipment.
- Response time: The faster, the better. Blitz's AC range responds in 25ns or less.
- Indication: A Green/Red window allows you to check the unit at a glance and an optional remote signalling contact is available to trigger an alert to the building management system.
- Standard: Check out IEC 61643- 11.
The best commercial surge protector is the one that's appropriate for your panel and your circumstances rather than the one with the highest kA rating. For more demanding projects, you'll want to engage an electrical consultant. You'll also need a panel schedule which will tell you the supply type and the rating of each board.
How to Install and Maintain SPDs in Commercial Buildings
Installation
- Installation should be done by a licensed electrician.
- The panel is switched off, and the SPD is fitted on the DIN rail with the backup protection the datasheet asks for.
- The earth connection is made with short, straight leads.
- For the full step-by-step process to install a surge protection device, our guide covers it.
Before commissioning
- Test the earthing. An SPD on a bad earth won't be able to get the surge current away properly.
- Make a note of the make, model and installation date of each unit on the panel schedule.
- Label each SPD to indicate which circuit it protects, so that if anyone opens the panel later, they'll know what's what.
Routine maintenance
- Maintenance is actually far easier than most people imagine.
- Look at the Green/Red window on the panel during any routine panel checks and after every bad storm or grid fault.
- Red indicates the unit has reached the end of its life and it's time to replace it.
- If you have the optional remote signalling contact, connect it to your building management system to get an alert.
Yearly checks
- Once a year, have an electrician check the earth continuity and terminal tightness on each SPD.
- Maintain a simple log of the status of each unit so that any change is immediately apparent.
- Keep a spare on hand for the critical panels (a failed SPD leaves the circuit unprotected until it's replaced).
- After a major lightning strike, have the earth connections and wiring checked in addition to the SPDs.
SPD Solutions for Offices and Buildings by Blitz Energy India
Blitz Energy India is a manufacturer of AC and DC surge protection devices, DC MCBs, and PV solar fuse products, designed and made in India. If you are looking for a commercial power surge protector for an office or building, the AC range covers both common panel layouts: single-phase and three-phase four-pole.
Both are Type 2 (Class II) per IEC 61643-11. Both have a 20kA nominal and 40kA max discharge current, a voltage protection level of 1.5kV or less and a response time of 25ns or less. Both mount on a 35mm DIN rail, both have a green/red status lamp and both have an optional remote signalling contact.
The products are made in a 50,000+ sq ft facility with 100% automated quality control and a zero defect policy. Blitz serves customers in 8+ countries. If you've got rooftop solar on your building, you can pair the AC range with Blitz DC SPDs (600V and 1000V rated). There is also after-sales support for any questions you may have about your panel.
Conclusion
Do not underestimate the importance of commercial surge protection devices in any place where there is a lot of equipment and appliances. You have to make sure that every level of your establishment is equipped with a functional device. Provide a proper grounding system and check all the pieces of equipment regularly. Thus, your offices, shopping malls, hospitals, and hotels will operate normally even during power surges.